| RXP 200: Pneum. Dual-channel, VAV master controller
How energy efficiency is improved Spreading the heating-cooling sequence during night mode and in the case of higher outside temperatures to save energy
Areas of application Creating a heating-cooling sequence with adjustable zone in combination with a room temperature controller, type TSP 80A, as well as a dual-channel volume flow controller, type RLP 100 F918.
Properties
- Controller front panel is printed with circuit diagram for rapid identification of function
- Thermoplastic housing suitable for wall or top-hat rail mounting (rail EN 60715)
- Compressed-air connections with Rp 1/8" female thread
- Low-pressure connections in form of stepped nipples for flexible plastic hose (internal Ø 4 and 6 mm)
- Complies with directive 97/23/EC Art. 3.3 on pressure equipment
Technical description
- Supply pressure 1.3 bar ± 0.1
- Three inputs for:
- outside temperature
- room temperature
- setpoint adjustment: 2 outputs for heating and cooling
|