RLP 100: Pneumatic air-volume controller

How energy efficiency is improved
Enables the demand-led volume flow control of fume cupboards, laboratory rooms and clean rooms.

Areas of application
Specially designed for volume flow control equipment in VAV installations. In combination with a highly accurate, static differential pressure transmitter and a pneumatic damper drive, it is possible to control laboratory fume cupboards, laboratory rooms and room pressures.

Properties

  • ATEX certification for use in Zone 1 potentially explosive areas
  • Conformity tested as per EN 13463-1 and EN 1127-1 (Ex II 2 G T6)
  • Control of constant, switchable or variable air volumes
  • Highly accurate, static differential pressure sensor with large measuring range (1 to 160 Pa)
  • Controller front panel is printed with circuit diagram for rapid identification of function
  • Glass-fibre-reinforced thermoplastic housing suitable for wall or top-hat rail mounting (rail EN 60715)
  • Compressed-air connections with Rp 1/8" female thread
  • Special measuring connection for recording the volume flow with M4 connector
  • Low-pressure connections in form of stepped nipples for flexible plastic hose (internal Ø 4 and 6 mm)
  • Complies with directive 97/23/EC Art. 3.3 on pressure equipment


Technical description

  • Supply pressure 1.3 bar ± 0.1
  • Response sensitivity of sensor 0.1 Pa
  • Linearity, square root extraction accuracy 2%
  • Two inputs for:
    • command variable
    • setpoint adjustment Δ
  • Two outputs for:
    • actual value
    • activation of damper drive
  • One adjuster for adjustment of the sensor measuring range
  • Three setpoint adjusters for maximum and minimum limiting of volume flow, plus limiting setpoint adjustment ΔV to max. ± 20%